Resource Guide 08

Lithium Battery Storage Laws — U.S. Overview

There is no single nationwide rule requiring every commercial lithium battery to be stored in the same type of cabinet or room. Storage requirements depend on the batteries, quantity, condition, activity, building and the codes adopted in the local jurisdiction.

The starting point

“What are the storage laws?” is really several questions.

Lithium battery storage can be affected by adopted fire and building codes, workplace-safety requirements, technical standards, local amendments, the battery condition and the way the storage area is being used.

A national model code can therefore provide an important framework without necessarily being the exact enforceable requirement at a particular facility.

Battery Safe Systems — practical interpretation Determine the jurisdiction and storage scenario before selecting the storage product.

A cabinet cannot make an unknown site requirement disappear. First establish what is being stored, how much is present, the condition of the batteries and which code edition the local authority applies.

Important Model-code requirements on this page should not be treated as automatically applicable nationwide.

States and local jurisdictions adopt different code editions and can make amendments. The Authority Having Jurisdiction should be used to resolve site-specific code and approval questions.

01
What counts as law?

A model code, a standard and an adopted requirement are not the same thing.

The International Fire Code is widely used across the United States, but it is a model code. It becomes enforceable through adoption by the relevant governmental jurisdiction, often with local amendments.

Technical standards such as NFPA documents can also become important where they are adopted, incorporated by reference, required by an authority or used as the accepted basis for a design.

Model code International Fire Code

Provides model fire-safety requirements that jurisdictions can adopt and amend.

Adoption State / local jurisdiction

Determines which edition and amendments have legal effect locally.

Enforcement AHJ / fire code official

Applies and interprets requirements for the particular site.

Code adoption International Code Council

ICC describes the IFC as a model code intended to be adopted under governmental procedures and notes that jurisdictions can amend the model code during adoption.

View ICC source ↗
Practical interpretation “The 2024 IFC says…” and “our facility is legally required to…” are different statements.

Confirm the adopted edition and amendments before converting a model-code provision into a procurement specification.

02
Classify the storage

Not every battery sitting in a building is the same storage scenario.

Before applying a storage requirement, establish what is actually present. Battery condition, packaging, energy, quantity and whether the battery is installed in equipment can materially change the applicable pathway.

Installed battery Battery already installed in equipment

This can fall outside provisions written specifically for stored loose batteries and may instead be addressed through equipment or application-specific requirements.

Retail / packaged New batteries in original packaging

Some model-code provisions provide specific exceptions or different treatment based on packaging and battery rating.

Commercial inventory Loose batteries awaiting use

Quantity, arrangement, fire area, battery energy and building conditions can become increasingly important.

Charging Stored batteries being charged

Charging introduces an active electrical process and should not be treated as identical to passive storage.

Damaged Suspect or damaged batteries

Batteries that have left normal service require a separate assessment and isolation pathway rather than routine storage.

ESS Stationary Energy Storage System

An installed ESS has its own developed code and standards framework and should not be confused with loose battery inventory.

Battery type Condition Installed or loose? Quantity / energy Indoor / outdoor Applicable pathway
Review Battery Inventory & Site Risk Assessment
03
Current model-code example

The 2024 IFC introduced a dedicated lithium battery storage framework.

Section 320 of the 2024 International Fire Code addresses storage of lithium-ion and lithium-metal batteries. It distinguishes limited indoor storage, larger indoor storage areas and outdoor storage.

The section also contains exceptions, meaning the presence of a lithium battery does not automatically place every battery within the same Section 320 requirements.

IFC 320.1 Scope & exceptions

Defines the general storage scope and identifies battery situations excluded from the section.

IFC 320.2 Permits

The 2024 model code establishes a permit trigger for certain accumulations exceeding 15 cubic feet.

IFC 320.3 Fire safety plan

Requires a fire safety plan addressing emergency response for covered lithium battery storage.

IFC 320.4.1 Limited indoor storage

Provides a container-based pathway for not more than 15 cubic feet of covered battery storage.

IFC 320.4.2 Indoor storage areas

Introduces more substantial requirements where the limited-storage pathway is not used.

IFC 320.4.3 Outdoor storage

Addresses separation, storage-area size and fire detection for covered outdoor storage.

Do not skip this step The 15-cubic-foot figure is a 2024 IFC model-code provision — not a universal U.S. legal threshold.

A facility could be located in a jurisdiction using an earlier edition, a locally amended edition or another fire-code framework. Verify local adoption before using this number as the basis of design.

Primary source 2024 International Fire Code — Section 320

The current model-code text includes scope, permit, fire-safety-plan, indoor-storage and outdoor-storage requirements for lithium-ion and lithium-metal batteries.

View IFC source ↗
2024 IFC Section 320.1

The model code also identifies important exceptions.

These exceptions reinforce why the exact battery scenario needs to be established before applying the storage rules.

01 Batteries installed in the equipment, devices or vehicles they are designed to power
02 Certain new or refurbished batteries packed for use with their intended equipment
03 Certain batteries in original retail packaging, including lithium-ion batteries rated at not more than 300 Wh
04 Temporary storage during specified battery manufacturing processes
05 Temporary storage during specified vehicle manufacturing or repair processes
Practical interpretation An exception from one code section does not mean “no safety requirements apply.”

Other fire-code provisions, workplace-safety requirements, manufacturer instructions and local rules may still be relevant.

04
Indoor storage

The 2024 IFC separates limited container storage from larger indoor storage areas.

IFC 320.4.1 Limited indoor storage

The model code permits not more than 15 cubic feet of covered batteries to be stored through a specified container arrangement.

  • Open-top noncombustible containers or approved battery-collection containers
  • Individual containers or groups limited to 7.5 cubic feet
  • Separation between container groups
  • Separation from exits and exit-access doors
IFC 320.4.2 Indoor storage areas

Storage outside the limited-container pathway brings a more developed fire and explosion protection framework into the current model code.

  • Technical opinion and report
  • Fire-resistance separation where applicable
  • Automatic sprinkler or approved suppression system
  • Automatic fire detection and alarm
  • Explosion control where recommended by the approved report
Larger indoor storage The current model code moves beyond simply specifying “a fireproof cabinet.”

For covered indoor storage areas, the 2024 IFC requires a technical opinion and report evaluating fire and explosion risks and addressing subjects such as possible flammable-gas deflagration and the basis of design for fire suppression.

State of charge The 2024 IFC also recognises battery state of charge.

Section 320.4.2.6 provides reduced requirements for certain indoor storage areas where lithium-ion batteries have a demonstrated state of charge not exceeding 30 percent and approved procedures ensure that limit is maintained.

Battery Safe Systems — practical interpretation Quantity alone is not the whole storage question.

Packaging, state of charge, storage arrangement, building construction, detection, suppression and local approval can all affect the final requirement.

05
Outdoor & special storage

Moving batteries outdoors changes the requirement — it does not remove it.

Outdoor storage can reduce some building exposures, but the current IFC model code still addresses separation from buildings and other exposures, storage-area dimensions and automatic fire detection.

Separation Distance from exposures

The 2024 model code includes separation options involving distance, rated construction or approved prefabricated structures.

Area Storage-area limits

The current model code limits individual outdoor storage areas and requires separation between multiple storage areas.

Height Storage configuration

Maximum storage height forms part of the current outdoor-storage provisions.

Detection Automatic fire detection

Covered outdoor storage areas require an approved automatic fire detection and alarm system under the 2024 model code.

Micromobility deserves separate attention E-bike and e-scooter battery operations can also fall within dedicated IFC provisions.

The 2024 IFC contains separate provisions for powered micromobility devices, including charging equipment, charging areas, removable batteries and fire-safety planning. A commercial fleet should therefore not assume that general loose-battery storage is the only relevant code section.

Review Battery Charging Best Practices →
Damaged batteries A battery that is damaged or suspect should not simply be treated as ordinary inventory.

Once condition becomes uncertain, the operational question changes from normal storage toward assessment, separation and controlled disposition.

Explore Damaged Battery Isolation →
06
Other layers

Fire-code storage requirements sit alongside workplace safety and technical standards.

OSHA Workplace safety

OSHA does not currently provide one lithium-ion-specific storage standard, but its existing workplace standards and General Duty Clause can become relevant to battery hazards and employee exposure.

OSHA workplace guide →
NFPA 855 Stationary energy storage — and lithium battery storage

NFPA 855 is the Standard for the Installation of Stationary Energy Storage Systems. The 2026 edition also contains Chapter 14, dedicated to storage of lithium-metal or lithium-ion batteries.

NFPA 855 source ↗
AHJ Local approval

The fire code official or other Authority Having Jurisdiction can be central to determining what code applies and whether a proposed storage arrangement is acceptable.

Fire Codes, NFPA, UL & AHJ →
Important distinction A stationary ESS and a warehouse containing loose rechargeable batteries are not automatically the same code problem.

Establish whether the batteries form an installed energy-storage system or are being stored as inventory before applying ESS terminology, testing requirements or standards.

07
Practical compliance process

A sensible storage decision starts with the site — not the cabinet catalogue.

01
Define the battery inventory

Type, chemistry where known, Wh, quantity, packaging and battery condition.

02
Define the activity

Passive storage, charging, retail stock, damaged-battery isolation, manufacturing or stationary energy storage.

03
Define the storage quantity

Do not rely on battery count alone. Establish the measurements relevant to the applicable code.

04
Identify the jurisdiction

State, county and city can affect the adopted fire and building code.

05
Confirm the adopted code edition

Determine whether the jurisdiction uses the 2024 IFC, another edition or a different regulatory framework.

06
Check local amendments

Model-code language may have been modified during adoption.

07
Define the required safety capabilities

Separation, fire resistance, suppression, detection, ventilation, monitoring or other controls should follow the requirement.

08
Verify the proposed solution with stakeholders

Where required, confirm the arrangement with the AHJ, fire authority, EHS team, insurer or other responsible party.

Before buying storage equipment
What specific requirement are we trying to satisfy? What code edition and section supports that requirement? Does the product documentation address that capability? What batteries and energy levels were used in testing? Does the evidence apply to our intended configuration? Does the AHJ need to approve the proposed arrangement?
Inventory Jurisdiction Adopted code Requirement Capability Product evidence
Battery Safe Systems — practical interpretation “Fire-resistant battery cabinet” is a product description. It is not a complete code analysis.

The stronger procurement route is to establish the applicable requirement first and then determine whether the proposed cabinet, room, locker, container or other system provides the capabilities and evidence needed for that requirement.

From requirement into solution

Storage format should follow the identified requirement.

Cabinets, lockers, rooms, outdoor structures and combined storage-and-charging systems provide different capabilities and should not be treated as interchangeable.

Primary references

Verify the code and edition behind the requirement.

Code adoption and standards evolve. Check the current jurisdiction, edition and applicability before treating a provision as a legal requirement for a particular site.

Need to translate the storage requirement into a system?

Start with the batteries, site and operating conditions.

Battery Safe Systems can help organise the storage requirement and compare suitable cabinet, locker, room, outdoor or combined storage-and-charging approaches.

Start a Guided Assessment